K2XLF24-5 Buck Boost Transformer FT0329

Standard Price: $1,129.41
TEMCo Direct: $903.28
( saved $226.13 )
No reviews yet Write a Review
SKU:
FT0329
UPC:
708281060354
Availability:
Usually ships within 24 hours
Weight:
110.00 LBS
Shipping:
$361.69 (Fixed Shipping Cost)

This versatile transformer will produce any of the below voltage combinations. Verify that your application falls under the capactiy given in amps or kVA for the voltage combination selected. If you would like to increase or reduce the capacity beyond what this model offers, see the Equivalent Models table above.


Boost Voltage (Increase) - SINGLE PHASE
Input Volts Output Volts kVA Amps Connection Diagram
200 220 45.8 208 1 - view »
208 229 47.7 208 1 - view »
220 242 50.4 208 1 - view »
230 276 28.8 104 2 - view »
240 264 55 208 1 - view »
380 418 43.5 104 4 - view »
416 458 47.7 104 4 - view »
430 473 49.3 104 4 - view »
435 457 95.2 208 3 - view »
436 480 50 104 4 - view »
440 462 96.3 208 3 - view »
440 484 50.4 104 4 - view »
450 473 98.4 208 3 - view »
456 479 99.8 208 3 - view »
460 483 101 208 3 - view »
480 504 105 208 3 - view »
Buck Voltage (Reduce) - SINGLE PHASE
Input Volts Output Volts kVA Amps Connection Diagram
220 200 45.8 229 1 - view »
229 208 47.7 229 1 - view »
242 220 50.4 229 1 - view »
276 230 28.8 125 2 - view »
264 240 55 229 1 - view »
418 380 43.5 115 4 - view »
458 416 47.7 115 4 - view »
473 430 49.3 115 4 - view »
457 435 95.2 219 3 - view »
480 436 50 115 4 - view »
462 440 96.3 219 3 - view »
484 440 50.4 115 4 - view »
473 450 98.4 219 3 - view »
479 456 99.8 219 3 - view »
483 460 101 219 3 - view »
504 480 105 219 3 - view »


Boost Voltage (Increase) - THREE PHASE
Input Volts Output Volts kVA Amps Qty Required Connection Diagram
173 208 37.5 104 2 5 - view »
200 240 43.3 104 2 5 - view »
208 250 45 104 2 5 - view »
362 380 144 208 2 6 - view »
380 418 75.4 104 2 7 - view »
400 440 79.4 104 2 7 - view »
419 440 166 208 2 8 - view »
436 480 86.5 104 2 7 - view »
457 480 181 208 2 8 - view »
480 528 95.3 104 2 7 - view »
480 504 182 208 2 8 - view »
346Y200 416Y240 75 104 3 9 - view »
379Y219 456Y263 82.2 104 3 9 - view »
400Y231 480Y277 86.6 104 3 9 - view »
416Y240 499Y288 90 104 3 9 - view »
Buck Voltage (Reduce) - THREE PHASE
Input Volts Output Volts kVA Amps Qty Required Connection Diagram
208 173 37.5 125 2 5 - view »
240 200 43.3 125 2 5 - view »
250 208 45 125 2 5 - view »
380 362 144 229 2 6 - view »
418 380 75.4 115 2 7 - view »
440 400 79.4 115 2 7 - view »
440 419 166 229 2 8 - view »
480 436 86.5 115 2 7 - view »
480 457 181 229 2 8 - view »
528 480 95.3 115 2 7 - view »
504 480 182 219 2 8 - view »
416Y240 346Y200 75 125 3 9 - view »
456Y263 379Y219 82.2 125 3 9 - view »
480Y277 400Y231 86.6 125 3 9 - view »
499Y288 416Y240 90 125 3 9 - view »
NOTE: Y configured units must have Y supply for proper operation.
Temperature Rise:
115
Insulation System:
180
Enclosure Rating:
NEMA 3R
Input Voltage:
240x480
Output Voltage:
24/48
Enclosure Material:
Steel
UL Listed:
Yes
CSA Approved:
Yes
Transformer Type:
Buck Boost
Phase:
Single
Kva:
5
Winding Material:
Copper
Primary Configuration:
Two Winding
Secondary Configuration:
Two Winding
Reverse Connectable:
Yes
Electrostatically Shielded:
No
Construction Style:
Enclosed - Encapsulated Core & Coil
Connection Type:
Wire leads
Frequency Hz:
60
K Rating:
1
Mounting Type:
Wall
Manufacturer Part Number:
K2XLF24-5