European Voltage Transformer Selection Guide (380, 400, 415 Volt, 3 Phase Output)
Selecting the right European voltage transformer is simple. To determine the best fit for your application, review the following considerations. Then, pick a transformer from one of the tables below.
Input VoltageWhat's your facility's supply voltage? Select a transformer that will operate on your facility's supply voltage. This will be 208V, 240V, 480V, 575V, or 600V. If your Voltage is 460V or 500V, pick a 480V transformer that supports either of these voltages. To ensure compatibility, check the connection diagram on each product page under "Support Information." FrequencyIf you're operating in the United States, you'll most likely be running on 60 Hz. Our Euro Standard Transformers can come rated for 50 Hz or 60 Hz with many larger ones dual rated 50/60 Hz, while our Euro Plus transformers operate exclusively on 60 Hz. WindingsCopper wound models cost more than the equivalent aluminum wound versions. The Primary advantage of copper is its superior corrosion resistance. Copper wound transformers are commonly used for corrosive or high humidity environments like marine applications, and when cost is not a factor. kVA or Amp OutputSelect a transformer with kVA based on your load requirements. We encourage you to oversize your transformer, but you should never undersize for your load. For motor loads, do not exceed 60% of the maximum capacity of the transformer, because electric motors have start up requirements much higher than their running requirements. It's okay to oversize significantly, but never to undersize. Stock & AvailabilityTEMCo Euro Plus transformers are more expensive since they have a lot more voltage options and are usually in stock for emergency situations where time is an issue. You can check the stock of a transformer by clicking on its part number in the tables below. Euro Standard Transformers are less expensive and have a 1.5 to 2 week production time for 350-2000 VA and 2 week production time for 3 KVA and up. |
IndexEuro Plus Transformers208, 240, 456, 480, 504 Volt Input » Euro Standard Transformers 208 Volt Input » 240 Volt Input » 480 Volt Input » 575 Volt Input » 600 Volt Input » Transformer Technical Terms Glossary » |
Euro Plus Transformers
208V, 240V, 456V, 480V, 504V Delta Primary x 380V, 400V, or 415V Wye Secondary
Usually in stock. To confirm stock status, check the individual product page.
3 Phase, 60 Hz, Dry Type NEMA 3R (rated for outdoor use). Dry type distribution transformer, enclosed ventilated.
kVA | Amps at 380V | Amps at 400V | Amps at 415V | Coils | Part Number |
3 | 4.56 | 4.33 | 4.17 | Copper | TT1000 |
6 | 9.12 | 8.66 | 8.35 | Copper | TT1001 |
9 | 13.67 | 12.99 | 12.52 | Copper | TT1002 |
15 | 22.79 | 21.65 | 20.87 | Aluminum | TT1003 |
30 | 45.58 | 43.30 | 41.74 | Aluminum | TT1004 |
45 | 68.37 | 64.95 | 62.61 | Aluminum | TT1005 |
75 | 113.95 | 108.26 | 104.34 | Aluminum | TT1006 |
112.5 | 170.93 | 162.38 | 156.52 | Aluminum | TT1007 |
150 | 227.91 | 216.51 | 208.69 | Aluminum | TT1008 |
225 | 341.86 | 324.77 | 313.03 | Aluminum | TT1009 |
300 | 455.82 | 433.03 | 417.37 | Aluminum | TT1010 |
500 | 759.69 | 721.71 | 695.62 | Aluminum | TT1011 |
Euro Standard Transformers
208V Delta Primary (Input) x 380V, 400V, or 415V Wye Secondary (Output)
3 Phase dry type distribution transformers.
1.5 to 2 Week Build Time. Copper wound. 50 or 60 Hz. Open or NEMA 1 Enclosed (rated for indoor use). | |||||||
kVA | Amps at 380V | Amps at 400V | Amps at 415V | Open Units | Enclosed Units | ||
50 Hz | 60 Hz | 50 Hz | 60 Hz | ||||
0.35 | 0.53 | 0.51 | 0.49 | TT1092 | TT1085 | TT1105 | TT1099 |
0.50 | 0.76 | 0.72 | 0.70 | TT1093 | TT1086 | TT1106 | TT1100 |
0.75 | 1.14 | 1.08 | 1.04 | TT1094 | TT1087 | TT1107 | TT1101 |
1.00 | 1.52 | 1.44 | 1.39 | TT1095 | TT1088 | TT1108 | TT1102 |
1.50 | 2.28 | 2.17 | 2.09 | TT1096 | TT1089 | TT1109 | TT1103 |
2.00 | 3.04 | 2.89 | 2.78 | TT1097 | TT1090 | TT1110 | TT1104 |
3.00 | 4.56 | 4.33 | 4.17 | TT1098 | TT1091 | N/A | N/A |
2 Week Build Time. 50/60 Hz. NEMA 3R enclosure (rated for outdoor use). | |||||||
kVA | Amps at 380V | Amps at 400V | Amps at 415V | Aluminum Wound | Copper Wound | ||
3 | 4.56 | 4.33 | 4.17 | N/A | TT1012 | ||
6 | 9.12 | 8.66 | 8.35 | N/A | TT1013 | ||
9 | 13.67 | 12.99 | 12.52 | N/A | TT1014 | ||
15 | 22.79 | 21.65 | 20.87 | TT1021 | TT1051 | ||
30 | 45.58 | 43.30 | 41.74 | TT1022 | TT1052 | ||
45 | 68.37 | 64.95 | 62.61 | TT1023 | TT1053 | ||
75 | 113.95 | 108.26 | 104.34 | TT1024 | TT1054 | ||
112.5 | 170.93 | 162.38 | 156.52 | TT1025 | TT1055 | ||
150 | 227.91 | 216.51 | 208.69 | TT1026 | TT1056 | ||
225 | 341.86 | 324.77 | 313.03 | TT1027 | TT1057 | ||
300 | 455.82 | 433.03 | 417.37 | TT1028 | TT1058 | ||
500 | 759.69 | 721.71 | 695.62 | TT1029 | TT1059 | ||
750 | 1139.54 | 1082.56 | 1043.43 | TT1030 | TT1060 |
240 Volt Delta Primary (Input) x 380V, 400V, or 415V Wye Secondary (Output)
3 phase dry type distribution transformers.
1.5 to 2 Week Build Time. Copper wound. 50 or 60 Hz. Open or NEMA 1 Enclosed (rated for indoor use). | |||||||
kVA | Amps at 380V | Amps at 400V | Amps at 415V | Open Units | Enclosed Units | ||
50 Hz | 60 Hz | 50 Hz | 60 Hz | ||||
0.35 | 0.53 | 0.51 | 0.49 | TT1118 | TT1111 | TT1131 | TT1125 |
0.50 | 0.76 | 0.72 | 0.70 | TT1119 | TT1112 | TT1132 | TT1126 |
0.75 | 1.14 | 1.08 | 1.04 | TT1120 | TT1113 | TT1133 | TT1127 |
1.00 | 1.52 | 1.44 | 1.39 | TT1121 | TT1114 | TT1134 | TT1128 |
1.50 | 2.28 | 2.17 | 2.09 | TT1122 | TT1115 | TT1135 | TT1129 |
2.00 | 3.04 | 2.89 | 2.78 | TT1123 | TT1116 | TT1136 | TT1130 |
3.00 | 4.56 | 4.33 | 4.17 | TT1124 | TT1117 | N/A | N/A |
2 Week Build Time. 50/60 Hz. NEMA 3R enclosure (rated for outdoor use). | |||||||
kVA | Amps at 380V | Amps at 400V | Amps at 415V | Aluminum Wound | Copper Wound | ||
3 | 4.56 | 4.33 | 4.17 | N/A | TT1015 | ||
6 | 9.12 | 8.66 | 8.35 | N/A | TT1016 | ||
9 | 13.67 | 12.99 | 12.52 | N/A | TT1017 | ||
15 | 22.79 | 21.65 | 20.87 | TT1031 | TT1061 | ||
30 | 45.58 | 43.30 | 41.74 | TT1032 | TT1062 | ||
45 | 68.37 | 64.95 | 62.61 | TT1033 | TT1063 | ||
75 | 113.95 | 108.26 | 104.34 | TT1034 | TT1064 | ||
112.5 | 170.93 | 162.38 | 156.52 | TT1035 | TT1065 | ||
150 | 227.91 | 216.51 | 208.69 | TT1036 | TT1066 | ||
225 | 341.86 | 324.77 | 313.03 | TT1037 | TT1067 | ||
300 | 455.82 | 433.03 | 417.37 | TT1038 | TT1068 | ||
500 | 759.69 | 721.71 | 695.62 | TT1039 | TT1069 | ||
750 | 1139.54 | 1082.56 | 1043.43 | TT1040 | TT1070 |
480V Delta Primary (Input) x 380V, 400V, or 415V Wye Secondary (Output)
3 Phase dry type distribution transformer.
1.5 to 2 Week Build Time. Copper wound. 50 or 60 Hz. Open or NEMA 1 Enclosed (rated for indoor use). | |||||||
kVA | Amps at 380V | Amps at 400V | Amps at 415V | Open Units | Enclosed Units | ||
50 Hz | 60 Hz | 50 Hz | 60 Hz | ||||
0.35 | 0.53 | 0.51 | 0.49 | TT1144 | TT1137 | TT1157 | TT1151 |
0.50 | 0.76 | 0.72 | 0.70 | TT1145 | TT1138 | TT1158 | TT1152 |
0.75 | 1.14 | 1.08 | 1.04 | TT1146 | TT1139 | TT1159 | TT1153 |
1.00 | 1.52 | 1.44 | 1.39 | TT1147 | TT1140 | TT1160 | TT1154 |
1.50 | 2.28 | 2.17 | 2.09 | TT1148 | TT1141 | TT1161 | TT1155 |
2.00 | 3.04 | 2.89 | 2.78 | TT1149 | TT1142 | TT1162 | TT1156 |
3.00 | 4.56 | 4.33 | 4.17 | TT1150 | TT1143 | N/A | N/A |
2 Week Build Time. 50/60 Hz. NEMA 3R enclosure (rated for outdoor use). | |||||||
kVA | Amps at 380V | Amps at 400V | Amps at 415V | Aluminum Wound | Copper Wound | ||
3 | 4.56 | 4.33 | 4.17 | N/A | TT1018 | ||
6 | 9.12 | 8.66 | 8.35 | N/A | TT1019 | ||
9 | 13.67 | 12.99 | 12.52 | N/A | TT1020 | ||
15 | 22.79 | 21.65 | 20.87 | TT1041 | TT1071 | ||
30 | 45.58 | 43.30 | 41.74 | TT1042 | TT1072 | ||
45 | 68.37 | 64.95 | 62.61 | TT1043 | TT1073 | ||
75 | 113.95 | 108.26 | 104.34 | TT1044 | TT1074 | ||
112.5 | 170.93 | 162.38 | 156.52 | TT1045 | TT1075 | ||
150 | 227.91 | 216.51 | 208.69 | TT1046 | TT1076 | ||
225 | 341.86 | 324.77 | 313.03 | TT1047 | TT1077 | ||
300 | 455.82 | 433.03 | 417.37 | TT1048 | TT1078 | ||
500 | 759.69 | 721.71 | 695.62 | TT1049 | TT1079 | ||
750 | 1139.54 | 1082.56 | 1043.43 | TT1050 | TT1080 |
575V Delta Primary (Input) x 380V, 400V, or 415V Wye Secondary (Output)
3 Phase dry type distribution transformer.
1.5 to 2 Week Build Time. Copper wound. 50 or 60 Hz. Open or NEMA 1 Enclosed (rated for indoor use). | |||||||
kVA | Amps at 380V | Amps at 400V | Amps at 415V | Open Units | Enclosed Units | ||
50 Hz | 60 Hz | 50 Hz | 60 Hz | ||||
0.35 | 0.53 | 0.51 | 0.49 | TT1170 | TT1163 | TT1183 | TT1177 |
0.50 | 0.76 | 0.72 | 0.70 | TT1171 | TT1164 | TT1184 | TT1178 |
0.75 | 1.14 | 1.08 | 1.04 | TT1172 | TT1165 | TT1185 | TT1179 |
1.00 | 1.52 | 1.44 | 1.39 | TT1173 | TT1166 | TT1186 | TT1180 |
1.50 | 2.28 | 2.17 | 2.09 | TT1174 | TT1167 | TT1187 | TT1181 |
2.00 | 3.04 | 2.89 | 2.78 | TT1175 | TT1168 | TT1188 | TT1182 |
3.00 | 4.56 | 4.33 | 4.17 | TT1176 | TT1169 | N/A | N/A |
2 Week Build Time. 50/60 Hz. NEMA 3R enclosure (rated for outdoor use). | |||||||
kVA | Amps at 380V | Amps at 400V | Amps at 415V | Aluminum Wound | Copper Wound | ||
3 | 4.56 | 4.33 | 4.17 | N/A | TT1199 | ||
6 | 9.12 | 8.66 | 8.35 | N/A | TT1200 | ||
9 | 13.67 | 12.99 | 12.52 | N/A | TT1201 | ||
15 | 22.79 | 21.65 | 20.87 | TT1189 | TT1202 | ||
30 | 45.58 | 43.30 | 41.74 | TT1190 | TT1203 | ||
45 | 68.37 | 64.95 | 62.61 | TT1191 | TT1204 | ||
75 | 113.95 | 108.26 | 104.34 | TT1192 | TT1205 | ||
112.5 | 170.93 | 162.38 | 156.52 | TT1193 | TT1206 | ||
150 | 227.91 | 216.51 | 208.69 | TT1194 | TT1207 | ||
225 | 341.86 | 324.77 | 313.03 | TT1195 | TT1208 | ||
300 | 455.82 | 433.03 | 417.37 | TT1196 | TT1209 | ||
500 | 759.69 | 721.71 | 695.62 | TT1197 | TT1210 | ||
750 | 1139.54 | 1082.56 | 1043.43 | TT1198 | TT1211 |
600V Delta Primary (Input) x 380V, 400V, or 415V Wye Secondary (Output)
3 Phase, dry type distribution transformer.
1.5 to 2 Week Build Time. Copper wound. 50 or 60 Hz. Open or NEMA 1 Enclosed (rated for indoor use). | |||||||
kVA | Amps at 380V | Amps at 400V | Amps at 415V | Open Units | Enclosed Units | ||
50 Hz | 60 Hz | 50 Hz | 60 Hz | ||||
0.35 | 0.53 | 0.51 | 0.49 | TT1218 | TT1211 | TT1225 | |
0.50 | 0.76 | 0.72 | 0.70 | TT1219 | TT1212 | TT1232 | TT1226 |
0.75 | 1.14 | 1.08 | 1.04 | TT1220 | TT1213 | TT1233 | TT1227 |
1.00 | 1.52 | 1.44 | 1.39 | TT1221 | TT1214 | TT1234 | TT1228 |
1.50 | 2.28 | 2.17 | 2.09 | TT1222 | TT1215 | TT1235 | TT1229 |
2.00 | 3.04 | 2.89 | 2.78 | TT1223 | TT1216 | TT1236 | TT1230 |
3.00 | 4.56 | 4.33 | 4.17 | TT1224 | TT1217 | N/A | N/A |
2 Week Build Time. 50/60 Hz. NEMA 3R enclosure (rated for outdoor use). | |||||||
kVA | Amps at 380V | Amps at 400V | Amps at 415V | Aluminum Wound | Copper Wound | ||
3 | 4.56 | 4.33 | 4.17 | N/A | TT1247 | ||
6 | 9.12 | 8.66 | 8.35 | N/A | TT1248 | ||
9 | 13.67 | 12.99 | 12.52 | N/A | TT1249 | ||
15 | 22.79 | 21.65 | 20.87 | TT1237 | TT1250 | ||
30 | 45.58 | 43.30 | 41.74 | TT1238 | TT1251 | ||
45 | 68.37 | 64.95 | 62.61 | TT1239 | TT1252 | ||
75 | 113.95 | 108.26 | 104.34 | TT1240 | TT1253 | ||
112.5 | 170.93 | 162.38 | 156.52 | TT1241 | TT1254 | ||
150 | 227.91 | 216.51 | 208.69 | TT1242 | TT1255 | ||
225 | 341.86 | 324.77 | 313.03 | TT1243 | TT1256 | ||
300 | 455.82 | 433.03 | 417.37 | TT1244 | TT1257 | ||
500 | 759.69 | 721.71 | 695.62 | TT1245 | TT1258 | ||
750 | 1139.54 | 1082.56 | 1043.43 | TT1246 | TT1259 |